Permit Number: T19CM09093
Parcel: 115023280

Address:
1850 N 6TH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T19CM09093
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2020 ANDREW CONNOR NPPO REVIEW Passed
09/16/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Per Technical Standard 10-01.6.1.E: Where residential driveways front directly on a major street, adequate area will be provided on site to accommodate a vehicular turnaround area or a circular driveway.
Show how this standard is met.
09/16/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
10/08/2020 NICHOLAS ROSS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Nicholas Martell
Planner

PROJECT: T19CM09093
1850 N 6th Ave
New 2 Story SFR
Residential (2nd Review)

TRANSMITTAL DATE: October 8, 2020

The porch addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The following comments have not been addressed, and require compliance before the plans can be approved by zoning:

1. 6th Street should be labeled as 6th Avenue.

2. The street perimeter yard setback is not shown correctly. As 6th Ave is designated as a collector on the COT Major Streets and Routes map the street perimeter yard setback is 21' or the height of the proposed building wall height, measured to the nearest edge of travel lane. Based on the elevations provided minimum street perimeter yard setback is 23'. Garage street perimeter yard setback is 19' to back of sidewalk and 18' to property line.

3. The proposed perimeter yard setback from the balcony wall to the northeast property line does not meet the minimum required by UDC Table 6.3-2.A. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line. Based on a wall height of 13'-4" the required perimeter yard setback is 8.87', proposed is 7.88'. A Design Development Option (DDO) will need to be processed and approved prior to approval of these plans.

4. As vehicle access is proposed off of a street designated as a collector on the COT Major Streets and Routes map demonstrate on the plan how a vehicle can back out of the garage and turn around on site prior to existing the parcel. All maneuvering must be on site.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov