Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM09069
Parcel: 140390380

Review Status: Active

Review Details: COMMERCIAL - NEW

Permit Number - T19CM09069
Review Name: COMMERCIAL - NEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2019 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
12/17/2019 ANY PLUMBING-COMMERCIAL REVIEW Active
12/17/2019 ANY ELECTRICAL-COMMERCIAL REVIEW Active
12/17/2019 ANY ZONING REVIEW Active
12/17/2019 ANY BUILDING-COMMERCIAL REVIEW Active
12/17/2019 ANY WATER REVIEW Active
12/17/2019 ANY MECHANICAL-COMMERCIAL REVIEW Active
12/17/2019 ANY ENGINEERING REVIEW Active
12/30/2019 MARTIN BROWN FIRE REVIEW Reqs Change Confirm address. The DP and building plan do not show the same address.
The Development Package for this project (DP19-0276) clearly indicates a fire sprinkler service line. The fire flow and distances from hydrants were calculated based on the installation of a fire sprinkler system. The architectural submittal indicates no sprinklers are required, and none will be provided. Either provide note on architecturals that sprinklers are to be installed, or the DP must be submitted again, along with a new water plan with a revised fire flow designation. Also, if no sprinklers are to be installed, a new hydrant will be required. Existing hydrant exceeds the 400' distance allowed for a building without sprinklers.