Permit Number: T19CM09046
Parcel: 136254100

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM09046
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2020 AMARTIN1 WATER REVIEW Passed RANDY MCCOY
12/11/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/11/2019 NMARTEL1 ZONING REVIEW Approved
12/11/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a #4 cu Grounding Electrode Conductor for the UFER. NEC 250.66B.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
12/11/2019 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Passed
12/11/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
12/11/2019 NMARTEL1 ENGINEERING REVIEW Passed
12/11/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Passed
12/12/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please provide code review analysis. Indicate whether fire sprinklers will be installed. Also, please indicate what will be stored in this building.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2020 AMARTIN1 OUT TO CUSTOMER Completed