Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM09046
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2020 | AMARTIN1 | WATER | REVIEW | Passed | RANDY MCCOY |
| 12/11/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/11/2019 | NMARTEL1 | ZONING | REVIEW | Approved | |
| 12/11/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a #4 cu Grounding Electrode Conductor for the UFER. NEC 250.66B. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
| 12/11/2019 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/11/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/11/2019 | NMARTEL1 | ENGINEERING | REVIEW | Passed | |
| 12/11/2019 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/12/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please provide code review analysis. Indicate whether fire sprinklers will be installed. Also, please indicate what will be stored in this building. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2020 | AMARTIN1 | OUT TO CUSTOMER | Completed |