Permit Number: T19CM09019
Parcel: 11206425B

Address:
2525 N TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM09019
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. As per the previous electrical plan review comments, "Provide electrical plans (all electrical plans) sealed by an Electrical Engineer registered in the State of Arizona".
Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304

Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.