01/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. By tapping the PV output feeders to the secondary transformer terminals, the transformer secondary feeders now have the potential of an additional 466 amps being imposed on them. Verify that the existing feeders and panels are protected from over current or, provide fused disconnect switches for each panel feeder at the point of the feeder connection. NEC 215.3, 240.4, 408.30 and 408.36.
2. Verify that the DG disconnect is rated for the highest available fault current likely to be imposed on it. NEC 690.15B
3. Provide information on the lighting plan that verifies that the added 25 luminaires will not overload the branch circuit and OCPD utilized. NEC 220.10, 225.8.
4. Show the location of all PV equipment and conduit routing on the site plans, including the location of the transformer vault. NEC 690, 705.
5. Verify that the existing transformers are listed by the manufacturer to be used in reverse. NEC 110.3
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
01/10/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change Approval of the development package is required prior to approval of the building plans
12/06/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
12/13/2019 MASHFOR1 FIRE REVIEW Approved
12/30/2019 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T19CM08960
Solar Canopy Install - Commercial (1st Review)
3033 E 6th St - R-3 Zoning

TRANSMITTAL DATE: December 30th, 2019

DUE DATE: January 7th, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The Canopy proposed to the north is in a Buildable area of a parcel located in a Residential zone. Detached accessory structures like solar canopies are not permitted in the full width of the lot between the principal building and the front street lot line, only in the side or the rear. (UDC 6.6.3.B)


02. COMMENT: If parking is to be restriped, provide parking calculations based on the use of the site showing that the new spaces meet the minimum number of required parking spaces.


03. COMMENT: Zoning will re-review the plans on the next submittal




If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 791-5550 or by email Iman.monshizadeh@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans