Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM08959
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/12/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide Section drawings for wheel chair lift enclosure for clarity . IBC 107.1.2. 2. Provide structural calculations for wheel chair enclosure framing noted on sheet A2 . 107.1.2. 3. Provide description, specifications, installation information, and cut sheets for wheel chair lift . IBC 107.1.2. 4. Provide connection details for partitions at roof/ceiling . IBC 107.2.1. Respond to plan review comments in writing . |
12/12/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/12/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a ventilation analysis using both ASHRAE Standard 62.1-2016 and the method shown in Section 808.2, IEBC 2018 for all areas in which the mechanical HVAC system is being rearranged or modified. 2. Provide the listing information for the proposed mini-split AC unit. 3. If the HVAC alternates are to be included in this activity, provide heating/cooling load and energy compliance calculations for the new AC units. 4. PRovide an exhaust vent for the relocated dryer. |
12/12/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Please provide complete electrical lighting and power plans as requested at the previous plan review. Provide plans sealed by an Electrical Engineer registered in the State of Arizona. 2. Provide electrical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
12/12/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a design for the water distribution systems (including the HW recirculation system) in each suite. 2. The fixture drain for a clothes washer shall discharge to a 3" or greater horizontal drain. 3. The minimum size of both upper and lower case lettering is 3/32". 4. Provide specifications for the two water heaters along with a detail showing all valves, temperature/pressure relief piping, safety pans, etc. |