Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM08959
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/06/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 12/06/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete electrical plans as explained to Samantha (owner rep). Also gave her a copy of the City of Tucson Plan Submittal Requirements. Revise the power and lighting plans to reflect this and re-submit. 2. Also provide compliance with NEC 517.13 , 406.12. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. Dan.santacruz@tucsonaz.gov |
| 12/06/2019 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/06/2019 | SARAH MEGGISON | ZONING | REVIEW | Approved | |
| 12/09/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1. Sheet A-1 - Carpentry Legend - 1. See Sheet A1.1 for details but A1.1 is not attached to plan set . Please clariry. IBC 107.2.1. 2. Provide details for wall connections to ceiling . IBC 1072.1. Respond to plan review comments in writting . |
| 12/12/2019 | AMARTIN1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/12/2019 | AMARTIN1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 12/12/2019 | AMARTIN1 | WATER | REVIEW | Needs Review |