Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM08935
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2019 | NMARTEL1 | ZONING | REVIEW | Approved | |
| 12/05/2019 | NMARTEL1 | ENGINEERING | REVIEW | Passed | |
| 12/05/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Indicate branch circuit and panel for the new receptacles. If utilizing existing branch circuits, please indicate this with a note on the plan. 2. Address any change in load. 3. If load increases, provide a complete panel schedule. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
| 12/05/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/05/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/06/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/06/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/06/2019 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/06/2019 | ROBERT SHERRY | WATER | REVIEW | Approved |