Permit Number: T19CM08933
Parcel: 13705501M

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T19CM08933
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The TRC Materials Plumbing Plan (2/P1.0) still shows an oil interceptor discharging to a storm drain. Connect the interceptor discharge to the sanitary waste system. Reference: Section 301.3, IPC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2020 JGARCIA1 APPROVAL SHELF Completed
07/28/2020 JGARCIA1 OUT TO CUSTOMER Completed
07/28/2020 JGARCIA1 REJECT SHELF Completed