Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM08933
Parcel: 13705501M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM08933
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Ref; Cover sheet T1.0. Revise the code references to the current adopted codes.
#1 Power plan sheet E2.0 is not sealed by a registrant.
#2 Revise the 2012 IECC Comcheck to 2018.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements.
01/10/2020 ROBERT SHERRY WATER REVIEW Completed
01/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The 2018 International Plumbing Code and the 2018 International Fuel Gas Code with their local amendments are the relevant codes for this project.
2. Provide the civil drawings associated with this activity. Reference: Section 107.2.1, IBC 2018.
3. Provide keynote #26 on sheet P1.0. Reference: Section 107.2.1, IBC 2018.
4. Provide a natural gas schematic showing the loads and developed lengths of the piping. Show that the existing natural gas piping is not undersized to support the added load. Reference: Section 107.2.1, IBC 2018.
5. Coordinate the plumbing plan (2/P1.0) and detail 3/P1.0 with respect to the venting. Air admittance valves require an engineering analysis for use with an oil interceptor. Reference: Section 107.2.1, IBC 2018 and Section 918.8, IPC 2018.
01/10/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The 2018 International Mechanical Code and the 2018 International Energy Conservation Code with their local amendments are the relevant codes for this project.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
3. Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
4. Show how adequate make-up air is to be provided to the room so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2018.
01/13/2020 MARTIN BROWN FIRE REVIEW Approved
01/13/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.0; Code Information: The codes listed should be revised to the 2018 International codes and the 2017 NEC. Please revise and verify all design meets the updated codes.
2. Sheet S0.1; Structural Notes (Governing Codes): The 2012 IBC is listed as the governing code. Please revise to the 2018 IBC and verify all design meets the updated code.
3. Sheet S1.0; Roof Framing Plan: On Grid C.6, a Detail 02/S3.0 is cut. Is this correct at that location? Please verify.
4. Sheet S1.0; Keyed Notes: Note 19 references Detail 19/S3.0. Please verify that reference.
5. Sheet S1.0; Keyed Notes: Note 23 references Detail 16/S3.0. Please verify that reference.
6. Sheet S2.0; Detail 20: A note references 17/S5.21 for the tube connection to the plate. Please revise that reference.
7. Structural Calculations: Please revise the listed governing code to the 2018 IBC and verify all structural design meets the updated code.
8. Structural Calculations: The Code Search for this project indicates the ASCE 7-10, while the reference in the 2018 IBC Indicates ASCE 7-16. Please revise and verify all structural design meets the updated code.
9. Structural Calculations: Loads were indicated for the roof framing members and the masonry wall footing, but no sizes were indicated in the calculations. Please provide.
10. Sheet A1.0; Keyed Notes: Note 14 references Detail 14/A3.0. Please verify that reference.
11. Sheet A1.0; Floor Plan: The exterior elevation at the west wall (Grid G) references 02/A1.0. Please revise that reference.
12. Sheet A1.0; Floor Plan: A Section 00/A3.1 is indicated on the south wall (Near Grid F). Please revise that section.
13. Sheet A1.0; Floor Plan: The exterior elevation at the south wall (Grid O) references 01/A1.0. Please revise that reference.
14. Sheet A1.1; Keyed Notes: Note 9 references Detail 08/A3.0 for an exterior bollard. Please revise that reference.
15. General: On the Special Inspection Certificate, please provide the name of the special inspector for each special inspection listed.
16. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov