Permit Number: T19CM08914
Parcel: 10408053K

Address:
4525 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM08914
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018.]
01/29/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/07/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. As requested per the previous electrical plan review, the plan reviewer could not locate a written response to the review comments in the second submittal.
2. Revise the Lighting Comcheck to 2018, also include exterior lighting.
3. Ref Plan Sheet E-1. Verify that the 75KVA transformer installed above the ceiling is not in violation of NEC art 450.13B.

Ref; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal requirements.