Permit Number: T19CM08850
Parcel: 13316030E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM08850
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2019 SAMUEL ROGERS ZONING REVIEW Approved
12/03/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/03/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/03/2019 SROGERS2 ENGINEERING REVIEW Passed
12/03/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Provide a drinking fountain as required in IBC Chapter 29 .

Respond to plan review comments in writting .
12/03/2019 ROBERT SHERRY WATER REVIEW Completed
12/03/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Water closet seats shall be sized for the water closet bowl type. Public restrooms are required to have elongated bowls. reference Section 425.2, IPC 2018.
2. Water closet seats in public restrooms are required to be the open-front type. Reference: Section 425.3, IPC 2018.
3. Provide drinking fountains.
12/03/2019 MARTIN BROWN FIRE REVIEW Approved
12/03/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed