Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM08824
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2019 | SARAH MEGGISON | ZONING | REVIEW | Approved | |
| 12/02/2019 | SMEGGIS1 | ENGINEERING | REVIEW | Passed | |
| 12/04/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/04/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/04/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.1; Code Summary: Please indicate on this sheet that the current revision is under the 2018 IBC. 2. Sheet A2.2D; Keynotes: Keynotes 3, 4, and 5 are not indicated on this plan. Please verify. 3. Sheet A2.20; Keynotes: Keynotes 1 through 3 and 5 through 12 are not indicated on this plan. Please verify. 4. Sheet A3.20; Keynotes: Keynote 2 is not indicated on this plan. Please verify. 5. General: Please provide written responses to all review comments. |
| 12/04/2019 | MROSS2 | FIRE | REVIEW | Approved | |
| 12/04/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/04/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/04/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |