Permit Number: T19CM08824
Parcel: 13707047A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM08824
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2019 SARAH MEGGISON ZONING REVIEW Approved
12/02/2019 SMEGGIS1 ENGINEERING REVIEW Passed
12/04/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
12/04/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.1; Code Summary: Please indicate on this sheet that the current revision is under the 2018 IBC.
2. Sheet A2.2D; Keynotes: Keynotes 3, 4, and 5 are not indicated on this plan. Please verify.
3. Sheet A2.20; Keynotes: Keynotes 1 through 3 and 5 through 12 are not indicated on this plan. Please verify.
4. Sheet A3.20; Keynotes: Keynote 2 is not indicated on this plan. Please verify.
5. General: Please provide written responses to all review comments.
12/04/2019 MROSS2 FIRE REVIEW Approved
12/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/04/2019 ROBERT SHERRY WATER REVIEW Completed
12/04/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed