Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM08762
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2020 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Arc-fault protection of circuits is required in 15 & 20 amp. outlets installed in kitchens, family rooms, dining rooms, living rooms, bedrooms, closets, hallways, laundry areas and similar rooms. Provide protection of outlets in these locations unless required to be GFCI protected. E3902.16 2. Nonlocking-type 15- and 20-ampere receptacles must be listed tamper-resistant receptacle devices on dwelling units. E4002.14. 3. Where two or more buildings are supplied from one service, each building must have a grounding electrode conductor and electrode. Show grounding requirements on the 1-line electrical plan. E3607.3 4. Where alterations or repairs to a building occur, the individual dwelling units must be equipped with a smoke alarm(s). Specify a smoke alarms in the single bedroom apartment and studio apartments in the sleeping areas. Ionization smoke alarms with an alarm-silencing switch shall not be installed less than 10 ft. horizontally from a permanently installed cooking appliance. R314.3.1. |
| 01/22/2020 | RMCCOY1 | WATER | REVIEW | Reqs Change | 1. Verify the maximum flow rates for the ¾" water meters specified in the WATER CALCULATION text boxes. The text boxes have different flow rates of 23 and 25 respectfully; verify proper size of water meter. IPC 106.3.1. 2. The potable water supply shall be protected from contamination due to cross connection of piping. Specify a backflow prevention device at the main water supply piping. IPC 608.1. |
| 01/22/2020 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. A hot water circulation and temperature maintenance system is a mandatory requirement for hot water distribution piping. Please specify method of compliance with section N1103.5.1. 2. Verify the maximum flow rates for the ¾" water meters specified in the WATER CALCULATION text boxes. The text boxes have different flow rates of 23 and 25 respectfully; verify proper size of water meter. IPC 106.3.1. |
| 01/22/2020 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Please clarify that the outdoor air intake opening CC50 is not less than 10 ft. from hazardous or noxious locations such as vents, chimneys, streets, alleys or parking lots. Site plan sheet X1.0 shows carports between each of the units. IRC R 303.5.1. 2. Access to the water heater or maintenance or replacement shall not require the dismantling or destruction of a permanent portion of the structure; provide an access for the water heater. M2005.2.1. 3. Provide a schematic drawing of the water heater which specifies the required controls and check valves for the hot water distribution circulation system. Specify an expansion tank at the water heater where a closed system of water piping occurs. M2003.1. 4. Where the clothes dryer is installed in a closet or enclosure, an opening having not less than 110 sq. in. shall be provided at the dryer location. IMC 504.6. |
| 01/23/2020 | MARTIN BROWN | FIRE | REVIEW | Approved |