Permit Number: T19CM08720
Parcel: 134030050

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM08720
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide Structural Calculations for roof structure . IBC 107.1.2.
2. Plans must be stamped by an Arizona Registrant . IBC 107.1., ARS 32-125.
12/04/2019 PAUL CAMARENA ZONING REVIEW Approved
12/13/2019 MASHFOR1 FIRE REVIEW Approved
12/23/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide electrical plans sealed by an Electrical Registrant registered in the State of Arizona.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements.
12/23/2019 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2020 TWEIDEM1 REJECT SHELF Completed