| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | The house is 3,728 sq ft and shall meet the required fire flow of 1,750 gpm for 2 hours from the nearest fire hydrant. If the fir eflow cannot be achieved then you will have to install fire sprinklers in the house. Please contact TW for the flow. Also need to know the distance from the hydrant to the furthest part of the house. Questions: Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
| 08/31/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed |