Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM08684
Parcel: 138072080

Address:
801 W MILTON ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM08684
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T19CM08684
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans including sheet 2.

FLOOR PLANS:

1. Show one-hour fire-resistive framed construction in compliance with IBC Table 721.1(2). Update ½” notation at he the Note on sheet 2. Both sides of framed walls require 1-hour ratings with 5/8” Type X or other listed material.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Update section B sheet 7.
2. An attic space requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Update section A sheet 7.

PLUMBING PLANS:

1. When specifying a gray drain line include a listed diverter valve and complete collection and discharge system consistent with P3009 for Recycling Systems with backflow and overflow provision. Consider a simplified dual clothes washer standpipe system.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.
2. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
08/03/2021 JPEELDA1 FIRE REVIEW Reqs Change The house is 3,728 sq ft and shall meet the required fire flow of 1,750 gpm for 2 hours from the nearest fire hydrant. If the fir eflow cannot be achieved then you will have to install fire sprinklers in the house. Please contact TW for the flow. Also need to know the distance from the hydrant to the furthest part of the house.
Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033