Permit Number: T19CM08583
Parcel: 124090770

Address:
116 N MARTIN AV

Review Status: Active

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM08583
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2019 SAMUEL ROGERS ZONING REVIEW Needs Review ZONING REVIEW TRANSMITTAL

FROM: Samuel Rogers
Planner

PROJECT:
T19CM08583
116 N MARTIN AV
DDO for living area in rear yard

TRANSMITTAL: 11/20/2019
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The proposed east setback is 20" and the proposed south setback is 37". The required east setback is 7.26' and the required south setback is 7.4'.
11/20/2019 SROGERS2 ENGINEERING REVIEW Passed
11/20/2019 SROGERS2 NPPO REVIEW Passed
11/20/2019 ANY BUILDING-RESIDENTIAL REVIEW Active