Permit Number: T19CM08567
Parcel: 14118605B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM08567
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Both the envelope compliance certificate and the interior lighting certificate indicate that the additional energy efiiciency requirement will be provided by installing a high efficiency HVAC system. Coordinate the response to Section C406.1, IECC 2018.
2. A keynote on sheet M2.1 calls for the condensate drains from the rooftop units to discharge over the nearest roof drain. 21. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
04/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change No crickets are shown on the architectural roof plan (A5.1) at the southwest parapet to direct the stormwater to the roof drains. Crickets are required to avoid excessive ponding along the parapet.
05/06/2020 MALLORY RESS ZONING REVIEW Reqs Change FROM: Mallory Ress
PDSD Zoning Review Section

PROJECT: T19CM08567 - Tropical smoothie Cafe
Building Plan Review (2nd Review) / Relate to [DP19-0260]
10230 E Old Vail / C-1 Zoning

TRANSMITTAL DATE: Mary 5, 2020


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact Mallory Ress at (520) 837-6933 or by email MALLORY.RESS@TUCSONAZ.GOV
05/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/06/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved