Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM08567
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please provide structural calculations for the foundation design for the light pole. This is item #12 of the plan review comments from the first review. The structural calculations do not contain the light pole design. |
| 02/04/2020 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The Interior Lighting Compliance Certificate provided is referencing the 1012 IECC. Please recalculate in accordance with the 2018 IECC which the City of Tucson has adopted. |
| 02/05/2020 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Plan review comment item #3: Provide calculations for the building envelope (e.g. COMcheck) to demonstrate compliance with the energy code; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. As a minimum, the information shall include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2018. Review comment: The COMcheck Envelope Compliance Certificate that was submitted in response to this comment item is citing the 2012 IECC; the City of Tucson has adopted the 2018 International Codes including the 2018 IECC. Please submit the envelope compliance report based off of the 2018 INTERNATIONAL ENERGY CONSERVATION CODE. Also, the Project Type under Project Information should be listed as New Construction, not Alteration. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. Review comment: Please coordinate the heating and cooling loads with the construction drawings. The roof shows R-30 insulation in the attic space which is different from the type shown in the HVAC load calculations. The construction of the walls is of wood frame construction, not metal framed as shown in the load calculations. 3. The Mechanical Compliance Certificate is citing the 2012 International Energy Code, not the 2018 IECC. Please address all comments in writing. |
| 02/05/2020 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Plumbing review comment #5. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2018. Review response: Please specify venting of the grease separator containment tank and the outlet trap to allow for the escape or admittance of air to compensate for the variable fluid level in the tank. IPC 1003.9. 2. Plumbing review comment #6. Show how stormwater will be directed to the roof drains to avoid excessive localized ponding. No crickets are shown on the architectural roof plan (A5.1). Reference: Section 1101.7, IPC 2018. Review response: Section 306.5 of the INTERNATIONAL MECHANICAL CODE requires that the access to ladder for roof mounted equipment to be provided at all times. In a storm event the access to the roof mounted equipment could be impeded if drainage water is directed to the access ladder location. IPC section 1106.5 specifies the use of parapet wall scuppers for storm water roof drainage systems. Specify crickets for directing storm water to roof drains and suppers and provode drainage calculations. IPC 1106.6 |
| 02/12/2020 | IMONSHI1 | ZONING | REVIEW | Reqs Change | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T19CM08567 - Tropical smoothie Cafe Building Plan Review (2nd Review) / Relate to [DP19-0260] 10230 E Old Vail / C-1 Zoning TRANSMITTAL DATE: February 12th, 2020 DUE DATE: February 25th, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans. 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. 3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 03/02/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 03/02/2020 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/15/2020 | LBOWERS1 | OUT TO CUSTOMER | Completed |
| 04/15/2020 | LBOWERS1 | REJECT SHELF | Completed |