Permit Number: T19CM08566
Parcel: 14042072B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM08566
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
12/11/2019 MARTIN BROWN FIRE REVIEW Approved
12/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/23/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide electrical specifications for the outlet devices.
2. Provide a complete luminaire schedule.
3. Any replaced receptacles to be tamper resistant Per NEC 406.4, 406.12(2).
4. Indicate circuiting for switches, Receptacles, Exhaust Fans, Luminaires, etc.
5. Specify mounting heights for switches, receptacles, per ADA requirements.
6. If these units have kitchens, extended branch circuits may need to be upgraded to ARC FAULT protection. See NEC 210.12C and 210.12D.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, ADA.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2020 SBORZAK1 REJECT SHELF Completed