Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM08566
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/11/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
12/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
12/23/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide electrical specifications for the outlet devices. 2. Provide a complete luminaire schedule. 3. Any replaced receptacles to be tamper resistant Per NEC 406.4, 406.12(2). 4. Indicate circuiting for switches, Receptacles, Exhaust Fans, Luminaires, etc. 5. Specify mounting heights for switches, receptacles, per ADA requirements. 6. If these units have kitchens, extended branch circuits may need to be upgraded to ARC FAULT protection. See NEC 210.12C and 210.12D. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, ADA. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/06/2020 | SBORZAK1 | REJECT SHELF | Completed |