Permit Number: T19CM08544
Parcel: 125080060

Address:
2250 E 8TH ST

Review Status: Active

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM08544
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2019 MALLORY RESS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Mallory Ress
Planner

PROJECT:
Permit # T19CM08544
2250 E 8th St
Add garage, add master bedroom and additional bedroom

TRANSMITTAL: 11/19/19
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b).

The applicant is proposing to add a garage with secondary access from Wilson Ave. The garage is proposed to be constructed at an angle to Wilson Ave. The setback varies from 2ft to 7ft. The garage is proposed at 12'6 in height. A 10 foot setback is required to Wilson Ave.

DDO is required.


The applicant is proposing to add a master bedroom and additional bedroom onto the east of the principle structure. The proposed height is 12'6". A 8.3' setback is required.

DDO is required.

There is an existing building in the southwest corner of property that appears not to have permits. A neighbor sign-off or a DDO is required.
11/19/2019 MRESS1 ENGINEERING REVIEW Passed
11/19/2019 MRESS1 NPPO REVIEW Passed
11/19/2019 ANY BUILDING-RESIDENTIAL REVIEW Active