Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM08511
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2019 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Completed | PER RANDY |
| 11/19/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Line Diagram. (a) Provide AIC rating of the pedestal coordinate with the utility co. (b) Show conduit, conductor sizes and types for the construction trailer feeder. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
| 11/19/2019 | KROBLES1 | ENGINEERING | REVIEW | Passed | |
| 11/19/2019 | SARAH MEGGISON | ZONING | REVIEW | Approved | |
| 11/20/2019 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/26/2019 | KROBLES1 | OUT TO CUSTOMER | Completed |