Permit Review Detail
Review Status: Active
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T19CM08457
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2019 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T19CM08457 Building Plans (1st Review) 4255 E KILMER ST - R-1 Zoning TRANSMITTAL DATE: November 19, 2019 DUE DATE: December 6, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments. 02. COMMENT: Provide zoning classification as a general note. 03. COMMENT: The required setback in a developing area per UDC section 6.4.5.C.2 (Within developing areas, the minimum required perimeter yard is determined by the type of building proposed and the projected average daily traffic (ADT) of the street and is required as follows:) The setback on Columbus BL is 21 ft measured from the back of future curb location. 04. COMMENT: The setback for the north west portion based on a wall height of 13'6" the required setback is 9.0'. 05. COMMENT: Dimension all setbacks, Dimension the setback from the west property line to the building. Provide the maximum width minimum width and average width. Dimension the right of way for Kilmer and Columbus. 06. COMMENT: It appear a board of Adjustment variance is required for the street setback along Columbus. If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 837-4082 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 12/06/2019 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T19CM08457 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. STRUCTURAL PLANS: 1. Identify each wall line needed for enclosing a complete rectangle with sides no greater than 60', Figure R602.10.1.1. Place these lines no further than 4' from an actual parallel wall, so that corners are no further than 10' from a "qualifying" braced wall panel. 2. Identify each braced wall panel associated with the four wall lines, Figure R602.10.2.2. Panel spacing may be no greater than 20' edge to edge. SECTIONS - DETAILS: 1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Sheet A.5 shows an unvented attic with insulation at the roof level, but sheets A.7 & A.8 show venting calculations needed when insulation is placed at the ceiling as shown at the roof detail at sheet S.2. 2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify sheet A.5. MECHANICAL PLANS: 1. Provide (an HVAC system with) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1507.3. Show the system and flow rate on the plans. ELECTRICAL PLANS: 1. Show the dishwasher/disposal with a dedicated 20A breaker, E3703.7. 2. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 12/17/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T19CM08457 1) The maximum width for a curb cut in a residential area is 20'. Plans show an approximate 24' wide curb cut. update as needed 2) Show on plans the dimension from the curb line of N Columbus Bl to the eastern side of the driveway. Minimum offset is 20' |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/17/2019 | SBORZAK1 | OUT TO CUSTOMER | Completed |