Permit Number: T19CM08414
Parcel: 125101480

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM08414
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Could not locate comcheck for lighting calcs in the 2nd submittal as stated in the comments response.
01/09/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change A copy of the Mechanical COMcheck was not included in the submittal. [Initial comment: Show that the proposed new HVAC equipment (e.g. RTU-17) meets the requirements of Sections C403.2, C403.3.2 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2018 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2018.]
01/09/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2020 SBORZAK1 REJECT SHELF Completed