Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM08414
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Could not locate comcheck for lighting calcs in the 2nd submittal as stated in the comments response. |
01/09/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | A copy of the Mechanical COMcheck was not included in the submittal. [Initial comment: Show that the proposed new HVAC equipment (e.g. RTU-17) meets the requirements of Sections C403.2, C403.3.2 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2018 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2018.] |
01/09/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/14/2020 | SBORZAK1 | REJECT SHELF | Completed |