Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM08414
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/19/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/20/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/21/2019 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
11/25/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/27/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of RTU-17. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Show that the proposed new HVAC equipment (e.g. RTU-17) meets the requirements of Sections C403.2, C403.3.2 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2018 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2018. 3. Provide exhaust for the fitting rooms. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018. |
11/27/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2018 IECC for the lighting. |
11/27/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/27/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide specifications for the new lavatories and lavatory faucets. Reference: Sections 303.4, 402 and 412.11, IPC 2018 as amended by the City of Tucson. |
12/03/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed |