Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/20/2019 MARTIN BROWN FIRE REVIEW Approved
11/21/2019 PAUL CAMARENA ZONING REVIEW Approved
11/25/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
11/27/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of RTU-17. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
2. Show that the proposed new HVAC equipment (e.g. RTU-17) meets the requirements of Sections C403.2, C403.3.2 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2018 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2018.
3. Provide exhaust for the fitting rooms. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018.
11/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the 2018 IECC for the lighting.
11/27/2019 ROBERT SHERRY WATER REVIEW Completed
11/27/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide specifications for the new lavatories and lavatory faucets. Reference: Sections 303.4, 402 and 412.11, IPC 2018 as amended by the City of Tucson.
12/03/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed