Permit Number: T19CM08412
Parcel: 137054470

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM08412
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2020 JOHN VAN WINKLE ENGINEERING REVIEW Approved
04/28/2020 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Steve Shields
Section Manager

PROJECT: Detached Solar Structure (Residential Use)
Building Plan (3rd Review) 742 W NEBRASKA ST
T19CM08412- R-2 Zoning

TRANSMITTAL DATE: April 28, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments.

02. COMMENT: As noted in the previous comment the minimum building setbacks to the side yard are the greatest of 6 feet or 2/3 the height of the structure side facing the west property line in this case. Based on the height added to the plot plan of 11'-4" the required perimeter yard setback to the west property line is 7'-6". Provide structure elevations so that the required perimeter yard setbacks can be verified.
Based on the 11'-4" height unless the structure can be placed 7'-6 feet from the property line the owner must obtain a setback waiver from the adjacent owner.

A statement can be added to the site plan whereby the adjacent owner acknowledges that he has no objection to the structure being constructed at 6'-6" as depicted on the site plan. See statement that needs to be added to the site plan. Staff will verify the property "owner" at the next review.

The adjacent owner's setback waiver statement must be added to the site plan. The following statement can be used.

"My Name is "ROSALINA GONZALEZ" and I am the owner of the property located at "750 W NEBRASKA ST". I have reviewed the site plan and I have no objection to the structure being located or constructed "6'-6" from the property line as depicted on the site plan".

Signature: _____________
Date: ________________

If you have any questions about this transmittal, Contact David Rivera at (520) 837-4957 or by email David.rivera@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans