Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM08397
Parcel: 137055760

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM08397
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2019 PAUL CAMARENA ZONING REVIEW Approved
11/29/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Illustrate the Exit Access Travel Distances on plan sheet G101. IBC 107.2.1.
12/09/2019 MARTIN BROWN FIRE REVIEW Approved
12/11/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
12/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
2. Verify that the metering faucets for the public lavatories will operate for at least 10-seconds for accessibility. Reference: Section 606.4, ICC/ANSI A117.1-09.
12/19/2019 ROBERT SHERRY WATER REVIEW Completed
12/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The City of Tucson has adopted the 2018 IMC as the approved method for calculating ventilation requirements, not ASHRAE 62.1. Verify the ventilation requirements for HP-7 and HP-8 using the occupant density given in Table 403.3.1.1, IMC 2018 (You may want to revise the room description from aerobics to weight room).
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2019 SBORZAK1 OUT TO CUSTOMER Completed