Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM08393
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/30/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 01/30/2020 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Per plan review comment No. 4; On the placard designations shown on the 1-line diagram on sheet AZ-513959, add placard #5 to the list of placards indicated for the inverters and verify compliance with NEC 690.12. |