Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM08393
Parcel: 13612834A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM08393
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Plans must be stamped by an Arizona Reqistrant .IBC 107.1.
2. Structural Calculations must be stamped by an Arizona Registrant . IBC 107.1.

Respond to plan review comments in writting .
12/11/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please review section 1204 of the 2018 International Fire Code. Clearly indicate on plans the roof access and pathways required under this section.
12/16/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a detail of the racking and for the grounding of the racking and PV Modules. Include hardware, listing information, manufacturer cut sheets. NEC 690.43
2. Provide manufacturer cut sheets for the inverter, optimizers, PV modules, utility disconnect switch. NEC 110.3, 690.4B
3. Ref; Site or roof plan. For clarity show on the plans, the conduit sizes and routing between electrical equipment. Also provide more detail on how the conduit penetrates or transitions from the rooftop to below the roof.
4. Indicate the location and equipment to be utilized as the Rapid Shutdown Initiation Device and where label # 5 is to be installed.
Ref; 2018 IBC 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements, (can be printed or downloaded from www.tucsonaz.gov/pdsd).

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2020 SBORZAK1 REJECT SHELF Completed
12/16/2019 SBORZAK1 OUT TO CUSTOMER Completed