Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM08393
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Plans must be stamped by an Arizona Reqistrant .IBC 107.1. 2. Structural Calculations must be stamped by an Arizona Registrant . IBC 107.1. Respond to plan review comments in writting . |
| 12/11/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please review section 1204 of the 2018 International Fire Code. Clearly indicate on plans the roof access and pathways required under this section. |
| 12/16/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a detail of the racking and for the grounding of the racking and PV Modules. Include hardware, listing information, manufacturer cut sheets. NEC 690.43 2. Provide manufacturer cut sheets for the inverter, optimizers, PV modules, utility disconnect switch. NEC 110.3, 690.4B 3. Ref; Site or roof plan. For clarity show on the plans, the conduit sizes and routing between electrical equipment. Also provide more detail on how the conduit penetrates or transitions from the rooftop to below the roof. 4. Indicate the location and equipment to be utilized as the Rapid Shutdown Initiation Device and where label # 5 is to be installed. Ref; 2018 IBC 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements, (can be printed or downloaded from www.tucsonaz.gov/pdsd). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/16/2020 | SBORZAK1 | REJECT SHELF | Completed |
| 12/16/2019 | SBORZAK1 | OUT TO CUSTOMER | Completed |