Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM08276
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/08/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Since the patio is being expanded, a new code analysis will be required on the drawing. This should include the new SF along with the new occupant load. Please revise the drawing accordingly. 2. General: Please indicate on the drawing if the existing patio cover is attached to the existing building. |
11/08/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/08/2019 | NMARTEL1 | ENGINEERING | REVIEW | Passed | |
11/08/2019 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Per the 2018 IFC, 903.2.1.2 Group A-2 occupant load and area require fire sprinklers. Documents to show fire sprinkler required Or clarify if the structure is stand alone |
11/08/2019 | NMARTEL1 | ZONING | REVIEW | Reqs Change | Does not match approved DP. Please correct and resubmit |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/14/2019 | QJONES1 | APPROVAL SHELF | Completed |
11/14/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
11/14/2019 | QJONES1 | REJECT SHELF | Completed |