Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM08273
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2020 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/02/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the piping arrangement for the hot water to lavatory LAV-7. If you intended to have the recirculation loop run by LAV-7 and then continue, connect the two hot water pipes and don't reduce the loop to ½", just run a ½" branch from the loop to the lavatory. Note that the requirement for the loop to be within 2-feet of LAV-7 does not apply to the LAV-1 lavatories - see Table C404.5.1, IECC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory (L7), complies with the requirements of Section C404.5, IECC 2018.] |