Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM08273
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/22/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/26/2019 | MROSS2 | FIRE | REVIEW | Approved | |
12/10/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Plan sheet E05.02 calls out using ASHRAE 90.1 and ComCheck for energy usage compliance. When choosing ASHRAE for the Energy Code for lighting, you must also use it for power. Provide compliance with the following. 2. Automatic Receptacle Control ASHRAE 90.1 8.4.2 (2013) [B]8.4.2 Automatic Receptacle Control The following shall be automatically controlled: a. At least 50% of all 125-volt 15- and 20-amp receptacles in all private offices, conference rooms, rooms used primarily for printing and/or copying functions, break rooms, classrooms, and individual workstations. Ref; 2018 IBC 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code (can be printed or downloaded from www.tucsonaz.gov/pdsd). |
12/16/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/16/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a metering or automatic faucet for the lavatory (L7), dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatory (L7), complies with the requirements of Section C404.5, IECC 2018. 3. Provide an approved vacuum relief valve (not a vacuum breaker as noted in detail L/P03.01) for the scheduled bottom-fed water heater that is located above the fixture outlets. Reference: Section 504.2, IPC 2018. |
12/16/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |