Permit Number: T19CM08262
Parcel: 121093720

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM08262
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2020 LOREN MAKUS ENGINEERING REVIEW Passed
04/09/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/13/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The second plan submittal did not contain revised Electrical plans, so the first review comments will apply to the third plan submittal.
2. The first plan review comment # 2. It was requested to provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code (OLC). The Comcheck is not the same as the OLC and will not substitute. Pal close attention to section 104 for information required on the plans for submittal.
3. The first plan review comment # 4. Ref; Plan Sheet E6.01. Provide a note at the LOAD SUMMARY table to (See 'MDP' panel schedule for load calcs).
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
04/24/2020 KROBLES1 ZONING REVIEW Needs Review