Permit Number: T19CM08262
Parcel: 121093720

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM08262
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 1; Sheet G0.01; Plumbing Fixtures: Per the IBC Section 2902.1.1, the total occupant load shall be divided in half to determine the occupant load of each sex. Fixture ratios shall be applied to the occupant load of each sex. Fractional numbers shall be rounded up. The total occupant load is 196 (98 males and 98 females). Male water closets required = 2.96 (3), and female water closets = 2.96 (3). Male lavatories required = 2.23 (3), and female lavatories required = 2.23 (3). Please verify the calculation.
2. Previous Comment 3; Sheet LS1.01; Wall Legend: Please indicate in the Wall Legend on Sheet LS1.01 the Smoke Barrier (SB) should include a one hour fire resistance rating.
3. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
01/27/2020 MARTIN BROWN FIRE REVIEW Reqs Change Please provide details and documentation that the exterior wall of the med gas room will comply with the ventilation requirements of section 5306.2.1 of the 2018 International Fire Code.
02/03/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the complete drawing set for review and approval.
2. Provide independent, secondary roof drains; the discharge point of the secondary roof drains shall be separate from the primary roof drains per Section 1108.2, IPC 2018. (Note that the roof drain configuration on sheet M2.01 is different than P1.02.)
02/03/2020 ROBERT SHERRY WATER REVIEW Completed
02/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The scope of ASHRAE Standard 170-2017 does not apply to spaces that are not for patient care or related support areas. The areas that are identified as non-regulated on sheet M0.02 require ventilation based on Section 403.3.1, IMC 2018. [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces per ASHRAE Standard 170-2017. Reference: Section 407.1, IMC 2018.]
02/06/2020 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM08262 - Tenant Improvement Building Plans (Commercial - Medical)
Building Plan Review (2nd Review) Tucson Surgery Center / Related to T19CM08261 / DP17-0182
2121 N. Craycroft Road - R-1 Zoning (to OCR-1 per Rezoning C9-16-16)

TRANSMITTAL DATE: February 6, 2020

DUE DATE: February 21, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.
***Previous zoning comments are still applicable.

1. COMMENT: Zoning has reviewed the tenant improvement plans for compliance with the Shell Building plans and development package DP17-0182. While the plans are consistent with the shell building plans and the approved DP, zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
02/25/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Second plan set not in the file.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2020 ARUIZ1 APPROVAL SHELF Completed
03/23/2020 ARUIZ1 OUT TO CUSTOMER Completed
03/23/2020 ARUIZ1 REJECT SHELF Completed