Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM08262
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide metering faucets for lavatories P-2 and P-6, each dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2018. 3. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2018. 6. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 01/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide calculations to verify that adequate ventilation will be provided for the occupied spaces per ASHRAE Standard 170-2017. Reference: Section 407.1, IMC 2018. |
| 01/06/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Reduced pressure backflow prevention assemblies for building water service are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 01/06/2020 | SBORZAK1 | ENGINEERING | REVIEW | Completed | |
| 12/11/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please review section 5306.2.1 of the 2018 International Fire Code and clearly indicate on plans that the Med Gas room will be 1 hour fire rated and will have a door with not less than two vents. |
| 12/17/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T19CM08262 - Tenant Improvement Building Plans (Commercial - Medical) Building Plan Review (1st Review) Tucson Surgery Center / Related to T19CM08261 / DP17-0182 2121 N. Craycroft Road - R-1 Zoning (to OCR-1 per Rezoning C9-16-16) TRANSMITTAL DATE: December 17, 2019 DUE DATE: January 3, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the tenant improvement plans for compliance with the Shell Building plans and development package DP17-0182. While the plans are consistent with the shell building plans and the approved DP, zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans. 2. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and the building plans can be approved by zoning. If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 12/18/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.01: Please provide the plumbing fixture calculations on this sheet per the IBC Table 2902.1. Indicate the minimum fixtures required and the actual fixtures provided. 2. Sheet G2.01; All Walls: Please provide the metal stud gauge for all walls, or provide a reference for the location of that information. 3. Sheet LS1.01; Wall Legend: Per the IBC Section 709.3, the smoke barrier (SB) should indicate a one hour fire resistance rating. Please verify. 4. Sheet LS1.01; Floor Plan: The corridor wall of Room 138 (Mech) indicates an unrated partition to deck. Should this be designated as a smoke partition? Please verify. 5. Sheet LS1.01; Floor Plan: Per the IBC Section 422.3.2, a refuge area shall be provided for each nonambulatory care recipient. Please indicate the area(s) to be designated as refuge area if required. 6. Sheet A2.00; Toilet Elevation 1: Please indicate the dimension from the back wall to the vertical grab bar per the ICC/ANSI Figure 604.5.1. 7. Sheet A6.52; Rainwater Leader Detail 11: This detail is numbered 11, as is the detail at column wrap B/7. Please revise as required. 8. Sheet A7.01; Door Schedule: Where is the door hardware schedule listed? Please verify. 9. Sheet A8.01; Copy/Work Area: The plan indicates an Elevation 2. Where is that elevation located? 10. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 12/27/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete compliance with the 2018 IECC for the interior and exterior lighting. 2. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. This Code can be downloaded from www.tucsonaz.gov/pdsd. 3. Ref; Power and Lighting Plans. Provide a note requiring wiring methods are to comply with NEC 517.13 and 517.31 if applicable. 4. Ref; Service Line Diagram, E6.01. (a) Provide complete load calcs for the service. (b) Provide a grounding detail for all the Transformers and Generator. (c) Provide a complete Fault Current Analysis. (d) Identify each feeder with a mark that correlates with the feeder schedule. (e) What does the circle symbol with the shaded triangles pointed to the feeders represent? (f) Provide for a selective coordination as required per NEC 517.17C, 700.32. (g) Identify the Generator as "Emergency", or "Standby". (h) Provide for signage or labels as required per NEC 700.10. 5. Ref; Panel Schedules. Include load calcs in amps with the panel schedules. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/23/2020 | SBORZAK1 | REJECT SHELF | Completed |