Review Status: Completed
Review Details: RESUB - SITE/GRADING ALL
Permit Number - T19CM08261
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a complete plan set for review. 1. Provide a site utility plan including the up and downstream manhole rim and invert elevations, first floor elevation, building sewer and water service line sizes, proposed location of connection to the public sewer, location and size of the water meter, and the size/location of the reduced pressure back flow prevention assembly (if present). 2. Provide independent, secondary roof drains; the discharge point of the secondary roof drains shall be separate from the primary roof drains per Section 1108.2, IPC 2018. |
| 01/30/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a complete plan set, heating/cooling calculations, and Mechanical COMcheck for review. 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Show that the proposed air-cooled chiller and HVAC equipment meet the minimum performance requirements of Section C403.3.2, IECC 2018 (e.g. provide COMcheck Mechanical Compliance Certificate). 3. Condensate drains shall be terminated at an approved disposal location. Discharging condensate to the roof is not acceptable. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. |
| 02/05/2020 | DJELLEN1 | ZONING | REVIEW | Reqs Change | FROM: David Jellen PDSD Zoning Review Section PROJECT: T19CM08261 - New Shell Building (Commercial - Medical) Building Plan Review (2nd Review) Tucson Surgery Center / Related to T19CM08262 / DP17-0182 2121 N. Craycroft Road - R-1 Zoning (to OCR-1 per Rezoning C9-16-16) TRANSMITTAL DATE: February 5, 2020 DUE DATE: February 14, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for compliance with the revised and approved development package DP17-0182. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans. 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. 3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact David Jellen at (520) 837-4082 or by email David.Jellen@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 02/14/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/18/2020 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |