Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
2. Show that the proposed air-cooled chiller and HVAC equipment meet the minimum performance requirements of Section C403.3.2, IECC 2018 (e.g. provide COMcheck Mechanical Compliance Certificate).
3. Condensate drains shall be terminated at an approved disposal location. Discharging condensate to the roof is not acceptable. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
01/03/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a site utility plan including the up and downstream manhole rim and invert elevations, first floor elevation, building sewer and water service line sizes, proposed location of connection to the public sewer, location and size of the water meter, and the size/location of the reduced pressure back flow prevention assembly (if present).
2. Provide independent, secondary roof drains; the discharge point of the secondary roof drains shall be separate from the primary roof drains per Section 1108.2, IPC 2018.
01/06/2020 SBORZAK1 ENGINEERING REVIEW Passed
12/10/2019 MARTIN BROWN FIRE REVIEW Approved
12/17/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM08261 - New Shell Building (Commercial - Medical)
Building Plan Review (1st Review) Tucson Surgery Center / Related to T19CM08262 / DP17-0182
2121 N. Craycroft Road - R-1 Zoning (to OCR-1 per Rezoning C9-16-16)

TRANSMITTAL DATE: December 17, 2019

DUE DATE: January 3, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the revised and approved development package DP17-0182. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
12/18/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G2.01; Unrated Partition Wall: Please provide the metal stud gauge for this wall, or provide a reference for the location of that information.
2. Sheet G2.01; One Hour Fire Barrier: Please provide the metal stud gauge for this wall, or provide a reference for the location of that information.
3. Sheet A4.51; Roof Scuttle Detail 4: Using the IBC Section 1011.12.2, verify and indicate on the detail the size of the roof hatch opening.
4. Sheet A5.01; Exterior Elevation 3: Please indicate the exterior door near Grid Line B on this elevation. See the Floor Plan on Sheet A1.51.
5. Sheet A6.21; Sections C, D, and D Alt.: Please provide a detail reference at the top of the stud wall.
6. Sheet A6.22; Sections E and F: Please provide a detail reference at the top of the stud wall.
7. Sheet A6.23; Section G: Please provide a detail reference at the top of the stud wall.
8. Sheet A6.24; Sections I and J: Please provide a detail reference at the top of the stud wall.
9. Sheet A6.25; Sections K, L, and M: Please provide a detail reference at the top of the stud wall.
10. Sheet A6.26; Section N: Please provide a detail reference at the top of the stud wall.
11. Sheet S1.00; General Notes (Foundation): Note 1 indicates a geotechnical report was used for the foundation design. Please provide that report.
12. General: Please provide the structural calculations for this project.
13. General: Please provide the Special Inspection Certificate with Parts A and B completed. Go to www.tucsonaz.gov/PDSD for this form.
14. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
12/24/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code and the 2018 IECC for the exterior lighting.
2. Provide a complete Line Diagram as outlined per the City of Tucson Commercial Plan Submittal Requirements (electrical) This document can be printed or downloaded from www.tucsonaz.gov. Or provide a note, "By Separate Permit", or similar.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2020 SBORZAK1 REJECT SHELF Completed