Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM08247
Parcel: 133090470

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM08247
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2019 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: Ground Mounted Solar Install
Development Package (1st Review) - I-1 Zoning
T19CM08247
7802 E Bellevue St

TRANSMITTAL DATE: 11/7/2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The ground mounted solar does not comply with the 20' setback requirement to the west. The site is in an RX-1 zone and is adjacent to a residential zone to the west requiring a 20' setback. The proposed setback is 16.9'. Revise the setback on next submittal. The plot plan property lines appear to be incorrect and have affected the setback calculation.



If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or Samuel.Rogers@tucsonaz.gov, or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
11/07/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
11/07/2019 SROGERS2 NPPO REVIEW Passed
11/12/2019 PMARTIN1 BUILDING-RESIDENTIAL REVIEW Needs Review