06/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The revised outdoor lighting calculations are not sufficient to verify complete compliance with the Outdoor Lighting Code. See section 104, (Plan, Permit Submittal requirements).

#1. The following errors were found in the Outdoor Lighting Calculations.

(a) Ref; Plan Sheets E0.1 and E2.0. The lighting area and option are not shown per table 401.1.

(b) The lumen calculations do not correlate between plan E0.1 and E2.0.

(c)Verify the correct parcel size in acres.

(d) Show total allowed lumens vs total proposed lumens. Include all luminaires, new and existing.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code,

City of Tucson Commercial Plan Submittal Requirements