Permit Number: T19CM08190
Parcel: 13629003F

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T19CM08190
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2020 ELISA HAMBLIN ZONING REVIEW Reqs Change FROM: Elisa Hamblin, AICP
PDSD Zoning Review

PROJECT: T19CM08190; Shade Covering
Building Plans (1st Revision)
8123 E Poinciana Dr.

TRANSMITTAL DATE: May 29, 2020
DUE DATE: June 5, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review comments were addressed.
1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. As a new structure (shade canopy) is proposed on site, a development package submittal is required. At a minimum the development package must show the site in question with relevant zoning information. A previously approved development package may be re-used with the changes illustrated, or a new development package may be created. Information on development package submittals can be found online here: https://www.tucsonaz.gov/pdsd/apply-permit#Development%20Package. The development package must be approved prior to approval of the building plans.
2. COMMENT: As currently illustrated on the building plans, the shade covering will not meet required setbacks to the adjacent property to the south. The required setback would be 77’0”. A request for reduced setbacks can be submitted through the Design Development Option (DDO). Additional information is available online here: https://www.tucsonaz.gov/files/pdsd/2019_DDO_for_Setback_and_Height_UDC.pdf. Once the development package is submitted and preliminary zoning comments are complete, you may apply for the DDO.
3. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the approved development package.
4. COMMENT: Once the plans have been reviewed and approved by the Commercial Plan Reviewers and zoning has verified consistency with the approved development package, the building plans can be approved by zoning.

If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov or (520) 837-4966.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans and approved version of the DP as reference.
05/29/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S3.0; Site Plan: A note indicates 5'-0" minimum distance to the property line. A canvas structure must meet the requirements of the IBC Table 602 for the fire separation distance. For the U Occupancy Group with IIB Construction, the fire separation distance must be greater than or equal to 10 feet to meet the fire resistance rating of 0. Please verify.
2. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found on the website at www.tucsonaz.gov/PDSD.
3. General: Please provide written responses to all review comments.
06/02/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide details for Equipotential Bonding of all metallic parts associated with the Shade Structure. NEC 680.26.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/05/2020 ARUIZ1 APPROVAL SHELF Completed
06/05/2020 ARUIZ1 OUT TO CUSTOMER Completed