Permit Number: T19CM08177
Parcel: 109250520

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM08177
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/23/2020 ROBERT SHERRY WATER REVIEW Completed
01/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Ready access is defined as, "That which enables a fixture, appliance or equipment to be directly reached without requiring the removal or movement of any panel, door or similar obstruction and without the use of a portable ladder, step stool or similar device." Locating an indirect waste receiver behind a cabinet door does not constitute ready access. Note that a floor drain be suitable for use as an indirect waste receptor due to the possibility of splashing or flooding. Adding a funnel top to a floor drain or installing a floor sink will resolve that issue. Reference: Sections 202 and 802.4, IPC 2018. [Initial comment: Indirect waste receptors shall be installed in locations with ready access. Reference: Sections 202 and 802.4, IPC 2018.]
01/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/29/2020 AMARTIN1 ELECTRICAL-COMMERCIAL REVIEW Needs Review