Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM08177
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/14/2019 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 11/19/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-0; Construction Codes: Please revise the UPC to the IPC. 2. Sheet A-0; Construction Codes: Please add the 2009 ICC/ANSI A117.1 accessibility code. 3. Sheet A-0; Egress Plan: Please add a note to this plan indicating the maximum travel distance of 100' per the IBC Table 1006.2.1. 4. Sheet A-2; Floor Plan Keynotes: Note 8 references ADA Section 603.2.3 for door swing clearance. Please revise that reference. 5. Sheet A-3; Ceiling Plan Keynotes: Note 1 references Detail A14/D-1 for ceiling blocking. Please revise that reference. 6. Sheet A-3; Ceiling Plan Keynotes: Note 2 references Detail A18/D-1 for ceiling blocking. Please revise that reference. 7. Sheet D-2; Detail P2: A note references the IBC Section 1607.7.2 for grab bar support requirements. Please revise that reference and the loading requirements. 8. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 11/19/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/02/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.4.2 through C403.4.2.3, IECC 2018. 3. Verify that the use of a 3" duct for the restroom exhaust is in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference: Section 304.1, IMC 2018. 4. Provide justification for the use of a Zone Air Distribution Effectiveness (Ez) of 1.0 for a ceiling supply, ceiling return using a gas-fired furnace. Reference: Section 403.3.1.1.1.2, IMC 2018. 5. Revise the mechanical design as required to avoid using the egress corridor as a return air duct. Reference: Section 601.2, IMC 2018. |
| 12/02/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify keynote #18 on sheet P-1. What is the nature of a dental console? Reference: Section 107.2.1, IBC 2018. 2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018. 3. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3, IPC 2018. 4. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 5. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018. 6. Reroute the hot water return for the recirculating hot water system to connect to the cold water inlet of the water heater. Reference: Section 607.2.2, IPC 2018. 7. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 8. The discharge from autoclaves, and reduced pressure zone backflow prevention assemblies require an air gap, not an air break. The connection to the tailpiece pf a sink is an air break. Reference: Section 802.1.3, IPC 2018. 9. Indirect waste receptors shall be installed in locations with ready access. Reference: Sections 202 and 802.4, IPC 2018. |
| 12/02/2019 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the size of the water meter and backflow preventer serving this address. The Tucson Water data indicates that a 1" meter is serving the suite. |
| 12/04/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a note on the power plan to provide compliance with NEC 517.13 for wiring methods. 2. Provide for tamper resistant receptacles as required per NEC 406.12 (5). 3. Provide plans sealed by an Electrical Engineer registered in the State of Arizona. Electrical Engineer to review the electrical one line diagram, show the AIC ratings for the meter base, disconnects, fuse types, all conduit, conductor sizes and types for the feeders between the termination can or CT can and the disconnect switches. Correlate electrical equipment ratings with the service load calcs. 4. Verify that the existing SES is rated for the increased load for Suite 121. 5. Provide a note to connect the emergency lighting with battery back up to an un-switched lighting circuit to maintain battery charge. per NEC 700. 6. Identify the exterior luminaires, correlate with the luminaire schedule and provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. Ref; 2018 IBC sec 107.2.1, 2017 NEC. Chapter 30 section R-4-30-302 Arizona State Board of Technical Registration Rules. City of Tucson Commercial Plan Submittal requirements. |
| 12/09/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/06/2020 | SBORZAK1 | OUT TO CUSTOMER | Completed |