Permit Number: T19CM08098
Parcel: 117170010

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T19CM08098
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2020 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/07/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please provide information regarding use of roof area. If it is going to be available to the tenents, provide occupancy load calculations.
11/08/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change
12/13/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to verify that adequate ventilation will be provided for the dwelling units. Reference: Section 403.3, IMC 2018 and Sections R403.6 and R503.1.2, IECC 2018.
12/13/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the keynotes on sheet P2.0. Reference: Section 107.2.1, IBC 2018.
2. The detail tags all refer to sheet P3.0 instead of P5.0 where they are actually shown. Reference: Section 107.2.1, IBC 2018.
3. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure (i.e. will the wall support the water heater without buckling?). Reference: Section 301.2, IPC 2018.
4. The plans show the installation of a PVC drainage stack on the exterior of the building (keynote 3 on sheet P3.0). How will the pipe be protected from damage and freezing? Reference: Sections 303.2 and 305.4, IPC 2018.
5. Clarify the specification for the water closets in the common area restrooms. It appears that the part number shown in the specification is for the tank, not the tank and stool together. It is therefore unclear if the specified water closet has a round-front or an elongated bowl or if it is ADA-compliant. Reference: Section 425.2, IPC 2018 and Section 107.2.1, IBC 2018.
6. Provide open-front water closet seats for the restrooms in the common area. Reference: Section 425.3, IPC 2018.
7. Provide a metering faucet for the common area lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
6. Provide a detail showing that the water heaters located above the ceilings will have adequate access and maintenance space. Reference: Sections 502.3 and 502.5, IPC 2018 and Article 210.70 (c), NEC 2017.
8. Show how the drainage stacks connect to the existing building drains (keynotes 2 and 3, sheet P3.0). Reference: Section 704.3, IPC 2018.
9. New service hot water systems shall comply with Section R403.5.1.1, IECC 2018. Reference: Section R503.1.3, IECC 2018.
12/13/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Clarify use of new roof deck. If deck is used for anything other than proposed residential use, the roof deck may be considered as an expansion of use. This would required a new site plan
12/13/2019 ROBERT SHERRY WATER REVIEW Completed
12/17/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM08098 - T.I. Existing Building
Building Plan Review (1st Review) Related to IID T19SA00161
188 E. Broadway Blvd. OCR-2 Zoning

TRANSMITTAL DATE: December 17, 2019

DUE DATE: December 4, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the tenant improvement plans but cannot approve them at this time. A IID application has been submitted for the proposed development which includes exterior work. Zoning cannot approve the building plans until the IID process has been completed and the plans can be compared to the IID application and any possible conditions applicable to the approval process. In addition zoning cannot approve the building plans until the Design Professional and PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Once the plans have been reviewed and approved by the Design Professional and PDSD Commercial Plan Reviewers and zoning has verified compliance with the IID conditions of approval the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
12/18/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved