Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T19CM08069
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the - Drilled Pier Foundation Layout page located in the structural calculations and attach to plan set. IBC 107.2.1. 2. Provide the - Slab Foundation Layout page located in the structural calculations and attach to plan set . IBC 107.2.1. |
| 11/05/2019 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 11/07/2019 | PMARTIN1 | COMMUNICATIONS | REVIEW | Approved | |
| 11/19/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide load calcs for the electrical service. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/22/2019 | KROBLES1 | OUT TO CUSTOMER | Completed |