Permit Number: T19CM08056
Parcel: 10818716A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM08056
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2019 PAUL CAMARENA ZONING REVIEW Approved
11/07/2019 MARTIN BROWN FIRE REVIEW Approved
11/13/2019 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/21/2019 ROBERT SHERRY WATER REVIEW Completed
11/21/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/03/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
12/11/2019 KROBLES1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.1; Interior Wall Type Legend: At Wall Types 1, 2, 3, 4, and 5, please reference Sheet T2.1 for the gauge of the metal studs.
2. Sheet A1.1; General Notes: Note 8 references a shelf above the mop sink to support the water heater. Please provide a detail of the shelf construction on this sheet.
3. Sheet A4.1; Detail 1: Please indicate the number and size of the connectors for the diagonal bracing to the roof structure above and to the top of the partition wall.
4. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form is located on the City of Tucson website at www.tucsonaz.gov/PDSD.
5. General: Please provide written responses to all review comments.
12/11/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3, IMC 2018.
12/11/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018.
2. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. (Note that manufacturer's specification sheet for the proposed faucet states that it is "Not approved for commercial use".) Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.